L.l.How to adjust the regeneration time
Disconnect the power source.
Locate the three screws behind the manual regeneration knob by pushing the red button in and rotating the 24 hour dial until each screw appear in the cut out portion of the manual regeneration knob.
DLoosen each screw slightly to release the pressure on the time plate from the 24 hour gear.
?)Locate the generation time pointer on the inside of 24 hour dial in the cut out.
Turn the time plate so the desired regeneration time aligns next to the raised arrow.
Push the red button in and rotate the 24 hours dial. Tighten each of the three screws.

Файлы: 1 файл

Valve Start.docx

— 78.64 Кб (Скачать файл)

Valve Start-up Procedure


L.l.How to adjust the regeneration time
  1. Disconnect the power source.
  2. Locate the three screws behind the manual regeneration knob by pushing the red button in and rotating the 24 hour dial until each screw appear in the cut out portion of the manual regeneration knob.

DLoosen each screw slightly to release the pressure on the time plate from the 24 hour gear.

?)Locate the generation time pointer on the inside of 24 hour dial in the cut out.

  1. Turn the time plate so the desired regeneration time aligns next to the raised arrow.
  2. Push the red button in and rotate the 24 hours dial. Tighten each of the three screws.

2)Push the red button and locate the pointer one more time to ensure the desired regeneration time is correct.

DReset the time of day and restore power to the unit.

MOTE: the 24 hour gear would stop running when power off, it should be reset when the power switched on.

1.2.How to set the interval days of regeneration

The skipper wheel indicates 12 days on the timer model, every tab presents one day. the tab at the red pointer is today. Pull or push the tab to set the regeneration date. For example, firstly push down all the tabs then pull up the tab every other one, the valve will regenerate every other day. For example, pull all the skipper wheel pieces firstly, then pick up every other one, that means the regeneration date is regenerate one time every other day.

  1. Model Meter



 

NOTE: Immediate regeneration times do not have 24 hours gear, no time of day can be set. And they have same way to set the regeneration.

2.1.How to set the regeneration cycle program

® Pull out the cable from the meter.

© Set program wheel by lifting the middle small dial and rotating it until the desired capacity on the label aligned with the white dot.

® Release the middle small dial and check for firm engagement at setting.

® Rotate the manual regeneration knob and let the program wheel return to the position.

® Re-insert the meter cable back. 



 

  1. How to manual regenerate

Turn the manual regeneration knob clockwise until hear the clatter. This sight movement will switch on the micro switch attached and starts the regeneration. Program wheel would spend about 3 hours for rotate a cycle .it's also available to clockwise rotate manual regeneration knob until to the next desired regeneration steps, but before next step, please wait the motor running to corresponding regeneration step and stop.

NOTE: Don't rotate the manual regeneration knob before the motor stop. If the program wheel and piston on the valve runs in different position, please cut the power and check the valve position first, then rotate the manual regeneration knob to corresponding position, then apply the power again.

  1. How to set the regeneration cycle program



 

 

ф The regenerationwfle progrim on your water conditioner has been factory preset, however, portions of We cycle or program may be lengthened or shortened in time to suit local conditions.

© To expose cycle program wheel, grasp timer in upper left-hand corner and pull, releasing snap retainer and swinging timer to the right.

To change the regeneration cycle program the program wheel must be removed. Grasp program wheel and squeeze protruding lugs towards center, lift program wheel off timer.(Switch arms may require movement to facilitate removal.)

Return timer to closed positions engaging snap retainer in back plate. Make certain all electrical wires locate above snap retainer post.

 



 

Valve Start-up Procedure

How To Change The Length Of The Backwash Time:

The program wheel as shown in the drawing is in the service position. As you look at the numbered side of the program wheel, the group of pins starting at zero determines the length of time your unit will backwash.

FOR EXAMPLE: If there are six pins in this section, the time of backwash time will be 12 min. (2 min. Per pin).To change the length of backwash time, add or remove pins as required. The number of pins times two equals the backwash time in minutes.

How To Change The Length Of Brine And Rinse Time:

The group of holes between the last pin in the backwash section and the second group of pins determines the length of time that your unit will brine and rinse (2 min. Per hole.)

To change the length of brine and rinse time, move the rapid rinse group of pins to give more of fewer holes in the brine and rinse section. Number of holes time two equals brine and rinse time in the minutes.

How To Change The Length Of Rapid Rinse:

The second group of pins on the program wheel determines the length of time that your water conditioner will rapid rinse.(2 min. Per pin.)

To change the length of rapid time, add or remove pins at the higher numbered end of this section as required. The number of pins times two equals the rapid rinse time in minutes.

How To Change The Length Of Brine Tank Refill Time:

The second group of holes in the program wheel determines the length of time that your water conditioner will refill the brine tank.(2 min. Per hole.)

To change the length of refill time, move the two pins at the end of the second group of holes as required.

The regeneration cycle is complete when the outer micro-switch is tripped by the two pin set at end of the brine tank refill section. The program wheel, however, will continue to rotate until the inner micro-switch drops into the notch on the program wheel.